M300(A) MONITOR MODULE, C304(A) CONTROL MODULE, AND
I300(A) FAULT ISOLATOR MODULE INSTALLATION INSTRUCTIONS
This information is included as a quick reference installation guide. Refer to the appropriate Fire-Lite control panel installation man-
ual for detailed system information. If the modules will be installed in an existing operational system, inform the operator and local
authority that the system will be temporarily out of service. Disconnect power to the control panel before installing the modules.
STATUS LED
ROTARY DECADE
ADDRESS SWITCHES
MODE TABS
M300(A) MAGNET
TEST POSITION
A78-2318-01
Figure 1. Montior and Control Module
Conrols and Indicators
F300-03-01 1 I56-570-05
Fire-Lite Alarms, Inc., 12 Clintonville Rd, Northfield , CT 06472-1652 (203) 484-7161
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
M300(A) MONITOR MODULES provide a two-wire, or fault-tolerant, initiating
circuit for normally open contact fire alarm and supervisory devices, or either
normally open or normally closed security devices. The LED indicator can be
latched on or returned to the normal mode by code command from the panel.
Rotary decade switches are used to set the address of each module.
C304(A) CONTROL MODULES allow a compatible control panel to switch dis-
crete contacts by code command. The control module offers a status LED that
can be latched on or returned to the normal mode by code command from the
panel. Rotary decade switches are used to set the address of each module.
The control module offers two modes of switching operation. As shipped, the
module is configured for switching an external power source to notification ap-
pliances. The external power source can be a DC power supply or an audio amplifier (up to 70.7 Vrms). In this mode, the mod-
ule reports supervision status of the connected loads to the control panel. Load circuit status is reported as a normal, open, or
shorted circuit. Two pairs of output termination points are available for fault-tolerant wiring. The second mode of switching op-
eration allows the panel to control one Form-C (SPDT) set of contacts.
Circuit connections to the contacts are not
supervised
by the module.
This mode is enabled by breaking two external tabs on the module.
I300(A) FAULT ISOLATOR MODULES enable part of the communications loop to continue operating when a short circuit oc-
curs on it. An LED indicator blinks in the normal condition and turns on during a short circuit condition. The module will auto-
matically restore the entire communications loop to the normal condition when the short circuit is removed. (The isolator mod-
ule does not have decade switches.)
COMPATIBILITY REQUIREMENTS
To insure proper operation, these modules must be connected to addressable, listed compatible Fire-Lite control panels only.
MOUNTING M300(A), C304(A), AND I300(A) DEVICES
M300(A), C304(A), and I300(A) modules mount directly to 4 inch square elec-
trical boxes as shown in Figure 2A. The box must have a min. depth of 2
1
/8".
WIRING
NOTE: All wiring must conform to applicable local codes, ordinances, and
regulations. When using control modules in nonpower limited applica-
tions, the CB500 Module Barrier must be used to meet UL require-
ments for the separation of power-limited and nonpower-limited termi-
nals and wiring. The barrier must be inserted in a 4"x4"x2
1
/8" junction
box, and the control module must be placed into the barrier and at-
tached to the junction box (Figure 2A). The power-limited wiring must
be placed into the isolated quadrant of the module barrier (Figure 2B).
1. Install module wiring in accordance with the job drawings and appropriate
wiring diagrams (Figures 3 - 10).
2. Set the address on the M300 and C304 per job drawings. Record this ad-
dress and loop on the front of the module, if desired.
3. Secure module to electrical box (supplied by installer), as shown in Figure 2A.
M300(A) MAGNET TEST
The M300(A) Monitor module can be tested with Fire-Lite's M02-04-01 Test
Magnet (see Figure 1). The magnet test checks the module electronics and
connections to the control panel. Interfaced initiating and indicating devices
must be tested independently.
A78-2610-00
Figure 2A. Module
Mounting with Barrier
ISOLATED
QUADRANT
A78-2611-00
Figure 2B.
Seitenansicht 0
1 2 3 4

Inhaltsverzeichnis

Seite 1 - F300-03-01 1 I56-570-05

M300(A) MONITOR MODULE, C304(A) CONTROL MODULE, ANDI300(A) FAULT ISOLATOR MODULE INSTALLATION INSTRUCTIONSThis information is included as a quick refe

Seite 2 - F300-03-01 2 I56-570-05

A78-2281-03FIGURE 4. TYPICAL M300 FAULT TOLERANT INITIATING CIRCUIT CONFIGURATION, NFPA STYLE D1 (-)2 (+)MODULEFROM PANEL OR(+)(-)TO NEXT(+)(-)DEVICE(

Seite 3 - F300-03-01 3 I56-570-05

1 (–)2 (+)MODULEFROM PANEL OR(+)(–)TO NEXT(+)(–)DEVICE(+)(–)3 (–)4 (+)(+) 9(–) 8(–) 7(+) 6XXX 5CONTROL(–)(+)(–)(+)XXX - DO NOTUSE TERMINAL 5TO NEXT CO

Seite 4 - © Fire-Lite Alarms, Inc. 1996

F300-03-01 4 I56-570-05© Fire-Lite Alarms, Inc. 1996A78-2287-04FIGURE 10. I300 FAULT ISOLATOR MODULE WIRING1 (–)2 (+)MODULEFROM PANEL OR(+)(–)TO NEXT(