User’s Guidefor the 636 Pt Addr PanelPS-Tools
2 636 Pt Addr.PanelPS-Tools 04/2010IntroductionPS-Tools FeaturesPS-Tools provides many features such as:• Maintaining details of the fire panel custom
94 636 Pt Addr. PanelPS-Tools 04/2010TroubleshootingRing Count ErrorFault: The following message is displayed when you are connecting PS-Tools to th
636 Pt Addr. PanelPS-Tools 04/2010 95AAAAAppendixCoding SelectionThe Coding feature allows you to specify the type of output the main circuit board
96 50 Pt Addr PanelPS-Tools 04/2010Appendix4. If an Acknowledge switch is pressed, the NACs currently in 1st stage activation remain in 1st stage. Pr
PS-Tools User Guide636 Pt Addr. PanelPS-Tools 04/2010 IndexAAdding a New Customer 17Adding Customers 15Adding Devices 41Adding Modules 46ANN-80 Optio
636 Pt Addr.PanelPS-Tools 04/2010 LLogging On 14Loop Style 34NNAC (Notification Appliance Circuits) 29PPanel Secret Code 75PC/Printer Installed 34PC/P
636 Pt Addr.PanelPS-Tools 04/2010 322 Setting Up PS-ToolsThis chapter describes the procedures for installing and removing the PS-Tools.The followin
4 636 Pt Addr.PanelPS-Tools 04/2010Setting Up PS-ToolsSystem RequirementsBefore you begin the setup process, ensure that your laptop or computer has t
PS-Tools User Guide636 Pt Addr.PanelPS-Tools 04/2010 5Installing PS-ToolsTo install PS-Tools1. Insert the CD into the CD-ROM drive and go to the PS-
6 636 Pt Addr.PanelPS-Tools 04/2010Setting Up PS-Tools4. Click Change to change the destination folder. The Change Current Destination Folder dialog b
PS-Tools User Guide636 Pt Addr.PanelPS-Tools 04/2010 7Note• If there is no database of a previously installed PS-Tool, the Create new download passw
8 636 Pt Addr.PanelPS-Tools 04/2010Setting Up PS-Tools9. Click Next. The Setup Type dialog box appears.For Complete Setup10. Select Complete to instal
PS-Tools User Guide636 Pt Addr.PanelPS-Tools 04/2010 912. Click Install. A progress indicator appears, indicating the progress of installation to in
10 636 Pt Addr.PanelPS-Tools 04/2010Setting Up PS-Tools16. In the Custom Setup dialog box, select the option in the Server list to disable the PS-Tool
PS-Tools User Guide636 Pt Addr.PanelPS-Tools 04/2010 1120. Click Install. A progress indicator appears, indicating the progress of installation.21.
Fire Alarm System Limitations While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance! An automatic fire alarm
12 636 Pt Addr.PanelPS-Tools 04/2010Setting Up PS-ToolsRemoving PS-ToolsPS-Tools can be removed using the Control Panel.Removing PS-Tools using Contro
636 Pt Addr.PanelPS-Tools 04/2010 1333Getting StartedThis chapter describes how to log on to and quit the PS-Tools. The following table describes
14 636 Pt Addr.PanelPS-Tools 04/2010Getting StartedLogging OnTo log on to PS-Tools1. Click Start, and then choose Programs > PS-Tools > PS-Tools
636 Pt Addr.PanelPS-Tools 04/2010 1544 Adding CustomersUsing PS-Tools, you can configure the settings of the 636 Pt Addr. Fire Alarm Control Panel (
16 636 Pt Addr.PanelPS-Tools 04/2010Adding CustomersThe customer details window in the PS-Tools helps you to:• Add a new customer.• Find an existing c
PS-Tools User Guide636 Pt Addr. PanelPS-Tools 04/2010 17Adding a New CustomerA new customer can be the protection services staff for campuses such a
18 636 Pt Addr.PanelPS-Tools 04/2010Adding CustomersDuplicating a Customer RecordYou can also add a new customer in PS-Tools by making a copy of an ex
PS-Tools User Guide636 Pt Addr. PanelPS-Tools 04/2010 19Finding a CustomerUsing the Find option, you can find the details of a customer. You can sea
20 636 Pt Addr.PanelPS-Tools 04/2010Adding CustomersDeleting a CustomerWhen a customer account is considered inactive, you can delete the customer rec
636 Pt Addr.PanelPS-Tools 04/2010 2155 Configuring Fire PanelsUsing PS-Tools, you can configure the fire panel settings. Configuring a fire panel in
A fire alarm system does not operate without any electrical power. If AC power fails, the system operates from standby batteries only for a specified
22 636 Pt Addr.PanelPS-Tools 04/2010Configuring Fire PanelsDatabase Migration To migrate the information from PK-Plus to PS-Tools database.page 62Con
PS-Tools User Guide636 Pt Addr. PanelPS-Tools 04/2010 23Selecting Configuration TypeTo select a configuration type1. Using the Find option in the in
24 636 Pt Addr.PanelPS-Tools 04/2010Configuring Fire Panels5. SLC Loop Setup (see SLC Loop Setup)a. Detectors (see Detectors)b. Modules (see Modules)C
PS-Tools User Guide636 Pt Addr. PanelPS-Tools 04/2010 254. Type the addresses for Service Terminal1 and Service Terminal2.Central StationProgram the
26 636 Pt Addr.PanelPS-Tools 04/2010Configuring Fire PanelsFigure 5-2 Configuring Primary Central StationPrimary Central Station screen provides infor
PS-Tools User Guide636 Pt Addr. PanelPS-Tools 04/2010 278. Click Next or click Secondary Central Station in the left pane, to configure the secondar
28 636 Pt Addr.PanelPS-Tools 04/2010Configuring Fire PanelsRelayThe fire panel consists of one fixed and two programmable Form-C dry contact relays. T
PS-Tools User Guide636 Pt Addr. PanelPS-Tools 04/2010 29To configure the special zones1. Click Zone 97 - PAS to activate Zone 97 for a PAS (Positive
30 636 Pt Addr.PanelPS-Tools 04/2010Configuring Fire Panels3. Click NAC 1 - Silenceable to indicate if the notification appliance can be silenced by p
PS-Tools User Guide636 Pt Addr. PanelPS-Tools 04/2010 31Configuring General System SettingsYou can configure the timers, clock format, fire panel pa
FCC Warning WARNING: This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the ins
32 636 Pt Addr.PanelPS-Tools 04/2010Configuring Fire PanelsTimersYou can program the fire panel for PAS or Presignal operation, not both. If you set t
PS-Tools User Guide636 Pt Addr. PanelPS-Tools 04/2010 332. Type the Maintenance password to change the factory set password for maintenance level pr
34 636 Pt Addr.PanelPS-Tools 04/2010Configuring Fire PanelsLoop StyleIn Loop 1 and Loop 2, select the wiring style for the loop. The wiring style can
PS-Tools User Guide636 Pt Addr. PanelPS-Tools 04/2010 35Configuring Optional ModulesThe optional modules installed in the 636 Pt Addr. system includ
36 636 Pt Addr.PanelPS-Tools 04/2010Configuring Fire PanelsConfiguring ANN BUSANN-BUS is a communication terminal in the fire panel over which differe
PS-Tools User Guide636 Pt Addr. PanelPS-Tools 04/2010 37The ANN S/PG and ANN 80 settings are applicable globally for any ANN BUS address of the same
38 636 Pt Addr.PanelPS-Tools 04/2010Configuring Fire PanelsANN-AUDIOThe ANN-AUDIO 25/50 ZS All Call Zone series audio panel is used to play an audio m
PS-Tools User Guide636 Pt Addr. PanelPS-Tools 04/2010 39Figure 5-8 Configuring Primary ANN Bus2. In Primary ANN Bus Address, select the Module Type
40 636 Pt Addr.PanelPS-Tools 04/2010Configuring Fire PanelsDetectorsThe SLC Loop Setup -> Detectors pane helps you to perform the following:• Add a
PS-Tools User Guide636 Pt Addr. PanelPS-Tools 04/2010 41•Click Graphical View option to view a pictorial representation of all the devices in the SL
Table of Contents1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
42 636 Pt Addr.PanelPS-Tools 04/2010Configuring Fire PanelsTo add an addressable device to the SLC Loop1. In SLC Loop Setup -> Detectors pane, clic
PS-Tools User Guide636 Pt Addr. PanelPS-Tools 04/2010 4311. To enable the PAS option for the device, click PAS Enabled. The PAS option programs the
44 636 Pt Addr.PanelPS-Tools 04/2010Configuring Fire Panels2. Click Edit Device(s) to edit the device information. The Edit dialog box appears.3. Upda
PS-Tools User Guide636 Pt Addr. PanelPS-Tools 04/2010 45Finding DevicesUsing the Search option, you can find a device when there are multiple device
46 636 Pt Addr.PanelPS-Tools 04/2010Configuring Fire PanelsViewing ModulesYou can view all the addressable devices in tabular or graphical view. •Clic
PS-Tools User Guide636 Pt Addr. PanelPS-Tools 04/2010 47To add an addressable device to the SLC Loop1. In the SLC Loop Setup -> Modules pane, cli
48 636 Pt Addr.PanelPS-Tools 04/2010Configuring Fire Panels12. You can map each module to five Zones. Type the two digit number corresponding to the z
PS-Tools User Guide636 Pt Addr. PanelPS-Tools 04/2010 49To delete the modules in the SLC loop1. Select the check box corresponding to the module you
50 636 Pt Addr.PanelPS-Tools 04/2010Configuring Fire PanelsSave as TemplateTo save the configuration information as a template1. Click Save As Templa
PS-Tools User Guide636 Pt Addr. PanelPS-Tools 04/2010 514. Click Verify Setup to check the mapping of the input and output devices.A warning in the
5.21 Deleting Template . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
52 636 Pt Addr.PanelPS-Tools 04/2010Configuring Fire PanelsSimulationThe Simulation feature helps to view the zone correlations for the installed devi
PS-Tools User Guide636 Pt Addr. PanelPS-Tools 04/2010 536. The Input devices are denoted by << in the displayed Results.Graphical ViewTo perfo
54 636 Pt Addr.PanelPS-Tools 04/2010Configuring Fire Panels8. To view the device-to-device mapping, click Show Device-to-Device I/O Simulation.9. Clic
PS-Tools User Guide636 Pt Addr. PanelPS-Tools 04/2010 55To change the password to download configuration data to the fire panel1. In the File menu i
56 636 Pt Addr.PanelPS-Tools 04/2010Configuring Fire PanelsWalktest DataWalktest is a feature which allows you to test the fire alarm system. The walk
PS-Tools User Guide636 Pt Addr. PanelPS-Tools 04/2010 57History DataThe history data lists all the events and event types such as alarms, troubles,
58 636 Pt Addr.PanelPS-Tools 04/2010Configuring Fire PanelsTroubleshoot DataThe troubleshoot data displays the actual voltage, freeze condition, combo
PS-Tools User Guide636 Pt Addr. PanelPS-Tools 04/2010 591. Choose Tools > Compare Configuration from the initial customer details window in PS-T
60 636 Pt Addr.PanelPS-Tools 04/2010Configuring Fire Panels10. Click Select Other Files to select another customer for configuration.11. Click Print t
PS-Tools User Guide636 Pt Addr. PanelPS-Tools 04/2010 61Database RestoreThere can be situations, where the current working database encounters probl
PS-Tools User Guide636 Pt Addr.PanelPS-Tools 04/2010 iiiAbout This GuideThis guide describes the procedures for installing PS-Tools and using PS-Too
62 636 Pt Addr.PanelPS-Tools 04/2010Configuring Fire PanelsDatabase MigrationUsing PS-Tools, you can migrate the database files from PK-Plus to PS-Too
PS-Tools User Guide636 Pt Addr. PanelPS-Tools 04/2010 633. Type the details of the customer and click OK. A message, informing you about the status
64 636 Pt Addr.PanelPS-Tools 04/2010Configuring Fire PanelsTo connect to the client database1. Choose Tools > Run from Database > Client Machine
PS-Tools User Guide636 Pt Addr. PanelPS-Tools 04/2010 65Viewing Last Configuration DateUsing PS-Tools, you can view the details of a particular cust
66 636 Pt Addr.PanelPS-Tools 04/2010Configuring Fire PanelsModifying Customer DetailsYou can modify or view the customer details from the database ser
PS-Tools User Guide636 Pt Addr. PanelPS-Tools 04/2010 67Importing ConfigurationYou can import configuration details from the panel to PS-Tools. To i
68 636 Pt Addr.PanelPS-Tools 04/2010Configuring Fire PanelsImporting all ConfigurationsUsing PS-Tools, You can import and update all the configuration
PS-Tools User Guide636 Pt Addr. PanelPS-Tools 04/2010 69Exporting ConfigurationThe export configuration option is used when the same configuration n
70 636 Pt Addr.PanelPS-Tools 04/2010Configuring Fire PanelsDeleting TemplateA configuration template can be deleted when it is no longer needed for fu
PS-Tools User Guide636 Pt Addr. PanelPS-Tools 04/2010 7166 Upload/Download Configuration DataThe configuration process is completed only when you do
iv 636 Pt Addr.PanelPS-Tools 04/2010Related DocumentsFor more information about topics that are relevant to the subject of this manual, refer to the f
72 636 Pt Addr. PanelPS-Tools 04/2010Upload/Download Configuration DataConnection SettingsThe connection settings option displays the details of the
PS-Tools User Guide636 Pt Addr. PanelPS-Tools 04/2010 7365. Click Clear to clear the displayed data if there are multiple lines of data to scroll th
74 636 Pt Addr. PanelPS-Tools 04/2010Upload/Download Configuration DataSerial Port SettingsTo view the serial port settings1. Using the Find option,
PS-Tools User Guide636 Pt Addr. PanelPS-Tools 04/2010 756Connect/Disconnect to Fire PanelThe fire panel can be connected through serial port and mod
76 636 Pt Addr. PanelPS-Tools 04/2010Upload/Download Configuration Data5. Click Set Secret Code at PC to change the secret code of the panel in PS-T
PS-Tools User Guide636 Pt Addr. PanelPS-Tools 04/2010 776Download Configuration Data to Fire PanelUsing Download to Panel option, you can download t
78 636 Pt Addr. PanelPS-Tools 04/2010Upload/Download Configuration DataNote• For first time configuration, under Download to Panel, you must select
PS-Tools User Guide636 Pt Addr. PanelPS-Tools 04/2010 796Note If the feature configured in PS-Tools is not present in the panel, a message is displa
80 636 Pt Addr. PanelPS-Tools 04/2010Upload/Download Configuration Data•In the Event Codes tab, you can view the information such as values configur
PS-Tools User Guide636 Pt Addr. PanelPS-Tools 04/2010 816Upload Configuration Information from Fire PanelUsing the Upload From Panel option, you can
636 Pt Addr.PanelPS-Tools 04/2010 111 IntroductionThis chapter provides an overview of the PS-Tools (Programming Software Tools) application and des
82 636 Pt Addr. PanelPS-Tools 04/2010Upload/Download Configuration DataNote• For first time configuration, under Upload from Panel, you must select
PS-Tools User Guide636 Pt Addr. PanelPS-Tools 04/2010 836Note If the feature configured in PS-Tools is not present in the panel, a message is displa
84 636 Pt Addr. PanelPS-Tools 04/2010Upload/Download Configuration Dataupload or download, details on central station, event codes description, acti
PS-Tools User Guide636 Pt Addr. PanelPS-Tools 04/2010 8565. Click Panel Reset to reset all the panel settings.6. Click Alarm Silence to silence all
PS-Tools User Guide636 Pt Addr.PanelPS-Tools 04/2010 8777 Generating ReportUsing the Reports option in PS-Tools, you can generate the configuration
PS-Tools User Guide636 Pt Addr. PanelPS-Tools 04/2010 8988TroubleshootingThis section provides information about the commonly encountered alarms, tr
90 636 Pt Addr. PanelPS-Tools 04/2010TroubleshootingThis happens when fire panel is sending panel information, alarms, or troubles to central statio
PS-Tools User Guide636 Pt Addr. PanelPS-Tools 04/2010 918PS-Tools Failed to Download Data to PanelProblem: The following message is displayed in PC
92 636 Pt Addr. PanelPS-Tools 04/2010TroubleshootingPS-Tools Failed to Upload Data from PanelProblem: The following message is displayed in PC Panel
PS-Tools User Guide636 Pt Addr. PanelPS-Tools 04/2010 938Request Denied for Verify Secret CodeProblem: The following message is displayed in PC Pane
Kommentare zu diesen Handbüchern